Home Products List All Products List All Products
|
Andel’s tried and tested Floodline multi-zone leak detection systems are well known for being the most reliable, effective and easy to use. The “Plug & Play Auto-Connect” system allows instant, foolproof connection for quick, no-hassle installation by any engineer, contractor or competent person.
Using a special version of the industry standard “RJ” type network connector, Floodline Plug & Play has universal acceptance. This robust, stable plug and socket system gives quick, easy, positive connection every time. Maintenance, replacement and modification couldn’t be easier.
Multi-8 8 Zone Detection Cable and patch-leader cables are available in a range of standard pre-terminated lengths. Other non-standard lengths can be supplied at no extra surcharge. All cables can also be cut and connected on site by trained engineers.
Standard lengths: 5m, 7.5m, 10m, 15m
Couplers: In/out couplers perform all connection and zone change functions. No setup or links to change. No wire stripping. No confusion.
SOL - Start of Line Connects Leader Cable to Detection Cable
Autocoupler Connects one detection cable zone to another. In-built system logic automatically sets its relative position and zone address.
EOL - End of line Terminates last zone in line
Click here for all data sheets |
|
 Floodline Remote Alarm The Floodline Remote Alarm unit provides a visual and audible warning of a leak or even a system fault.
The Remote Alarm can be mounted anywhere within the building and is connected back to the main Floodline Control Panel.
For example, the main control panel may be mounted in the security office but some form of repeat indicator is needed at the reception desk which is manned 24hrs.
Function: Remote alarm alert of main control panel status
Power: 12VDC, 37mA fed from main panel
Construction: ABS Plastic enclosure for internal use only
Dimensions: H85 x W142 x D57 mm
Fixing: Wall/surface mounted
Alarm Indicators: Flashing red LED for LEAK or SYSTEM FAULT (all alarms displayed continuously until corrected and reset at main control panel) Audible alarm
Controls: Keyswitch mute Auto Reset - resets when main panel is reset
Other, non-standard remote alarm units can be supplied to specific requirement.
We can also provide other communication options including AUTODIALLERS and DIGITAL Communicators. We would be pleased to discuss your requirements. Click here for all data sheets |
|
Junction Boxes Floodline Junction Boxes are an integral part of a Detection Cable/Tape system.
Three variations of the Junction Boxes are available: 1. One zone Junction Box for use with Single-Zone Tape 2. Four zone Junction Box for use with the “Multi-4” 4 Zone detection cable (screw terminal connections) 3. 8 Zone Junction Box for use with the “Multi-8” 8 Zone detection cable (IDC “KRONE” type terminal connections)
Function: Connects Leader Cable to Detection Cable/Tape End-of-line termination Zone change along multi-zone cable string
Applications: Install and connect on site Zone identification assists and confirms leak location Protective Guard Plate/mounting bracket available if required
Caution Tags Floodline Caution Tags are an integral part of a Detection Cable/Tape system.
Function: Warns of Detection Cable/Tape function Confirms zone number
Applications: Self adhesive wrap around Detection Cable/Tape
Leader Cable Andel supply dedicated leader cabling.
Used for connecting Floodline Sensors to Floodline Alarm Panels. and for branching between detection areas on the same detection string.
Andel’s purpose-made Leader Cable is all LSF0H construction for use in modern industrial/commercial environments. The core colours of the detection cable match the colours of the detection cable making installation simpler. |
|
|
The Multi-Zone Control Panel operates the network of leak detection zones. A zone can be a single point or many metres long and the whole network is continuously monitored for leaks and continuity. Zones are electrically isolated from each other and individually displayed so the system can accept and report any number of simultaneous or consecutive zone alarms - true multiple leak reporting - an alarm in one zone has no affect on the normal monitoring of its neighbours or the rest of the system.
LEDs provide clear and easy to understand status and alarm information. Output relays are provided for connection to remote alarm, BMS etc. Leak detection is shown clearly as LEAK. Sensor or cable damage or failure is shown as SYSTEM FAULT.
Function: Water/Liquid detection, Temperature, Humidity and Gas detection
Zone Capacity: 4, 8, 16, 32
Power: 110/230 VAC, 50/60Hz mains operated, 25Watts (32 zones 50watts), 12VDC internal + battery backup
Construction: Powder coated steel enclosure
Dimensions: H292 x W285 x D90 mm (4,8,16 zones) H360 x W455 x D130 mm (32 zones)
Fixing: Wall/Surface mounted (special mounting arrangements to order)
Monitoring: LEAK - continuous water/liquid detection - each zone reports separately SYSTEM FAULT - sensor or leader cable damage, failure or disconnection
Alarm Indicators: Flashing LEDs for LEAK or SYSTEM FAULT (all alarms displayed separately and continuously until corrected and reset) Audible alarm
Status Indicators: Mains power supply, battery operation, internal 12VDC supply, low battery, alarm accept (mute)
Controls: Mute (buzzer silence/alarm accept) button, security key-switch output disable/reset
Outputs: 1. LEAK in any zone - DPCO relay (5A @ 230VAC)
2. SYSTEM FAULT in any zone - SPCO relay (5A @ 230VAC)
3. Complete power fail - SPCO relay (5A @ 230VAC)
4. LEAK in each individual zone - SPCO relay - optional (1A @ 30VDC)
All relays have "clean" volt-free contacts
Click here for all data sheets |
|
 Floodline Leak 1.MkII The Floodline Leak 1.MkII is a self-contained single zone leak detection module specially designed for incorporation into other control/ alarm systems, air conditioning units and BMS etc. The module can be used with all Floodline sensors.
The compact module is din-rail mounted and screw terminals provide connections for the leak sensors, power input and volt-free contact output.
Function: Water/liquid detection
Zone Capacity: 1 Zone
Power: Multi-Voltage 12 or 24v, AC or DC
Construction: Housed within a polycarbonate enclosure.
Dimensions: Length 100mm, width 75mm, depth 22.5mm
Fixing: Din-rail mounted
Monitoring: LEAK- continuous water/liquid SYSTEM FAULT - sensor or leader cable damage, failure or disconnection
Alarm Indicators: Flashing LEDs for LEAK or SYSTEM FAULT All alarms displayed separately and continuously until corrected and reset if in manual mode
Status Indicators: Power Control Auto/Manual Reset
Outputs: Leak - system fault SPCO Relay 1Amp@24vdc
Click here for all data sheets |
|
|
The Floodline Groundhog Mk II is a self-contained, single-zone leak detection system which can be mounted vertically or horizontally. It can be connected to any control/building management system that has the facility to accept volt-free contacts.
Additional Floodline Point Sensors or Leak Detection Tape can be slaved off the Groundhog.
Function: Water/Liquid detection
Zone Capacity: 1
Power: Multi-voltage operation 12 or 24V AC or DC at 0.8watts
Construction: Built into a stainless steel Guard Plate which provides protection and assists fixing
Dimensions: L130 x W90 x D37 mm
Fixing: Fixed or free-standing on floor or in drip tray Vertically at base of wall or plant
Monitoring: LEAK - continuous water/liquid built-in sensor and aux sensor input SYSTEM FAULT - aux sensor or Leader Cable damage, failure or disconnection
Alarm Indicator: Flashing LEDs for LEAK and SYSTEM FAULT All alarms displayed separately and continuously until corrected and reset if in manual mode
Status Indicator: Power LED
Controls: Manual/Auto reset select Sensitivity setting
Outputs: Leak/system fault - SPCO Relay 1Amp@24Vdc
Click here for all data sheets |
|
 Floodline One-Zone Control Panel The Floodline One-Zone water leak detection control panel offers a low cost, stand-alone system where a small amount of detection is required. One or more Floodline sensors can be connected.
Output relays are provided for connection to remote alarm, BMS etc. LEDs provide clear and easy to understand status and alarm information.
Function: Water/Liquid detection, Temperature, Humidity and Gas detection
Zone Capacity: 1
Power: 110/230 VAC, 50/60Hz mains operated, 23Watts
Construction: Powder coated steel enclosure
Dimensions: H200 x W225 x D70 mm
Fixing: Wall/surface mounted (special mounting arrangements to order)
Monitoring: LEAK - continuous water/liquid detection SYSTEM FAULT - sensor or leader cable damage, failure or disconnection
Alarm Indicators: Flashing LEDs for LEAK or SYSTEM FAULT (all alarms displayed separately and continuously until corrected and reset) Audible alarm
Status Indicators: Mains power supply
Controls: Mute (buzzer silence) button Reset
Outputs: 1. LEAK - DPCO relay (5A @ 230VAC)
2. SYSTEM FAULT/Complete Power Fail - DPCO relay (5A @ 230VAC)
All relays have "clean" volt-free contacts Click here for all data sheets |
|
 Floodline 128 Multi-Zone Control Panel The 128 Multi-Zone System operates a network of leak detection cables and sensors up to a total of 128 zones. A zone can be a single point or many metres of detection cable and the whole network is continuously monitored for leaks and continuity. Zones are electrically isolated from each other and individually displayed so the system can accept and report any number of simultaneous or consecutive zone alarms. An alarm in one zone has no effect on the normal monitoring of its neighbours or the rest of the system.
The Floodline 128 Multi-Zone System consists of a control unit with full text display and a base unit for connection of the sensor network. The control unit provides clear and easy to understand status and alarm information.
Output relays are provided for connection to remote alarm, BMS etc. BMS connection can also be provided by RS232/RS485 communication. Leak detection is shown clearly as LEAK DETECTED. Sensor or cable damage or failure is shown as SHORT CIRCUIT or OPEN CIRCUIT.
Function: Water/Liquid detection, Temperature, Humidity and Gas Detection
Zone Capacity: 32, 64, 96, 128
Power: 110/230 VAC 50/60Hz mains operated 160 Watts (max), 12 VDC internal + battery backup
Construction: Base and control unit powder coated steel enclosure
Dimensions: Base Unit: H555 x W490 x D160mm Control Unit: H185 x W55 x D62mm
Fixing: Wall/surface mounted (special mounting arrangements to order)
Monitoring: LEAK - continuous water/liquid detection - each zone reports separately SHORT/OPEN CIRCUIT - sensor or leader cable damage, failure or disconnection
Display (control unit) Disconnected - connection cable between control unit and base unit damaged or disconnected
Display (control unit) Communication Failure - control unit and base unit damaged or disconnected
Module Communication Failure - Internal communication between base unit motherboard and 32 zone module/comms module failure
Remote Disconnected - connection cable between base unit and optional Floodline Remote Alarm damaged or disconnected
Alarm Indicators: Base Unit: Display (control unit) Disconnected, Display (control unit) Comms Failed Control Unit: Flashing LED for alarm active plus 20x4 LCD for text description of alarms
Status Indicators: Base Unit: Power On Control Unit: 20x4 LCD gives text description of system status plus flashing LED for any alarm
Control: Base Unit: None Control Unit: Mute (silence alarm), security keyswitch (to access menu system), menu, up, down and enter (to operate menu and scroll through alarms)
Output: 1. Leak in any zone - SPCO Relay (5A @ 230VAC) 2. System Fault - open, short circuit any zone - SPCO Relay (5A @ 230VAC) 3. Mains Fail - SPCO Relay (5A @ 230VAC) 4. Complete Power Failure - SPCO Relay (5A @ 230VAC) 5. Self Test - Low battery, comms failure, remote/display disconnected - SPCO Relay (5A @ 230VAC) 6. Leak in each individual zone - SPCO Relay Click here for all data sheets |
|
|
The Floodline Oil Sensor can be included as part of a larger water leak detection system or one or more can be used to provide a dedicated oil leak alarm system. Oil Sensors are connected to a standard Floodline Control Panel giving visual and audible alarm features in addition to the facility for onward, remote, communications to BMS etc.
Applications: Internal oil tanks Plant rooms Pump sets Backup generators
Detection: Activates with oil (or other liquid) Multiple re-use Instant return to use
Construction: High density plastic body/sensor Sealed against immersion Heavy duty stainless steel guard
Dimensions: Sensor: H71mm x W44mm x D25mm Guard Plate: H110mm x W105mm x D30mm
Fixing: Vertically at base of wall or apparatus using Guard Plate Floor - free standing or fixed using Guard Plate/bracket Tank/Sump etc requires special bracket
Click here for all data sheets
|
|
|
For high sensitivity applications where a more basic, low cost system is required. The Single Zone Tape is a very strong, easy to install sensor. The sensor can be wetted and dried any number of times. The zones can be any length but the usual length is between 5 and 15m.
Applications: In the voids below raised floors Above suspended ceilings Tie-wrapped to individual pipes Run in drip trays Laid around the base of an item of plant, apparatus or tank Laid in loops or wave pattern for general monitoring of larger areas No minimum or maximum length
Detection: Activates with any conductive liquid anywhere along its entire length Multiple re-use, dry and reset Easy to replace or splice-in new length if damaged or hopelessly contaminated
Construction: Polyester “woven” construction. No exposed conductors. Very high strength and abrasion resistance.
Dimensions: 20mm x 3mm thick. Supplied in any length either pre-connected at the factory or for cutting on site.
Fixing: Fix to floor or other surfaces with flat ribbon type clips or self-adhesive clips or tie-wraps. Detection Tape is laid loosely with warning labels attached at regular intervals to warn of its function
System: Connection can be made directly to any Floodline Control Panel/Unit or via Leader Cable
Click here for all data sheets |
|
The Floodline Point Sensor is a compact sensor for vertical or horizontal mounting. Water touching its stainless steel probes activates the alarm. Used with the stainless steel Floodline Guard Plate to give heavy duty physical protection and assist fixing and adjustment.
The Point Sensor is used where Detection Cable could be damaged or where some damp, minor wetting or spillage is expected or of little concern. The sensor can be connected in any number and/or combination with other Floodline sensors.
Applications: Plant rooms Solid floor area Basement/tunnels
Detection: Activates when any conductive liquid makes contact across the probes Multiple re-use Instant return to use after water is cleared up
Construction: High density plastic body, stainless steel/nickel plated brass probes Heavy duty, stainless steel Guard Plate Encapsulation option for immersion proofing
Dimensions: Sensor: H71mm x W44mm x D25mm Guard Plate: H110mm x W105mm x D30mm
Fixing: Base of wall or apparatus. Floor - free standing or fixed Tank/Sump etc. - requires special bracket plus immersion proofing
System: Connected in any number and/or combination with other Floodline sensors
Click here for all data sheets |
|
|
The Floodline Pipe-in-Pipe Sensor is based around a Point Sensor but designed for fitting into a female threaded socket provided at strategic points in the outer pipe. Short stainless steel probes extend into the cavity, or annulus, created between the inner and outer pipes. When liquid escapes into the cavity and contacts a sensor the alarm is activated. Two types of device are available for water and oil (oil/any liquid).
Applications: Double containment pipe or tanks High level alarm in tanks
Detection: Activates when any conductive liquid contacts the stainless steel probes or touches the tip (depending on the type of device used) Multiple re-use Instant return to use
Construction: High density plastic body, stainless steel probes fully encapsulated Resistant plastic tip (oil pipe-in-pipe)
Dimensions: Length of body approx 70mm, diameter 30mm
Fixing: ½” BSP fitting as standard (other sizes available)
Click here for all data sheets |
|
 Floodline Flexi-pad Sensor The Flexi-Pad Sensors have been specifically designed for laying in narrow voids (too small for point sensors) or wrapped around pipes at valves or joints where leaks are more likely to occur. The Flexi-Pad Sensor can be used singly, or in groups with a number of sensors being connected together to form one zone.
A removable fabric cover assists absorption and protects the sensing surfaces. Flexi-Pad Sensors can be wetted and dried any number of times provided the sensor element/fabric cover is not contaminated with a substance that irrevocably changes its electrical characteristics. Examples may be vending machine syrup, chemical floor treatments, paints etc. After wetting, the cover can be replaced with a spare or removed for drying.
Applications: Wrapped round pipes Placed in drip trays under plant or equipment
Detection: Activates with any conductive liquid. Once dry can be returned to use
Construction: Tough, flexible plastic sheet with bonded “carbon loaded” detection tracks. Complete with removable fabric cover.
Fixing: Lay loose, pin/glue at corners or tie-wrap loosely around pipe
Dimensions: Sensor 400mm x 300mm x 1mm (16mm at connection point) Envelope 430mm x 350mm x 1mm
Leader Cable: Standard PVC/PVC 7/0.2 multi-core alarm/comms type cable or similar. LSF or other light cables can be substituted as required. 10m pre-fitted unless otherwise specified.
Bespoke Designs: Andel Ltd can offer a custom design service. The Flexi-Pad Sensor’s size, shape and base material can be tailored to the client’s individual requirements.
Typical clients for this service are CLEAN ROOM EQUIPMENT MANUFACTURERS and PROCESS EQUIPMENT MANUFACTURERS. Click here for all data sheets |
|
|
Super Absorbent - High Sensitivity
Multi-4 - 4 Zone Detection Cable has been used for over ten years in areas where maximum leak detection sensitivity is essential.
Although superceded by Andel's more modern Multi-8 all-polymer detection cables for general usage, the highly absorbent Multi-4 cable is the best option where sensitvity to the smallest amount of water or condensation is required.
One length of Multi-4 - 4 Zone Detection Cable can provide up to four separately reporting zones. The zone changeover points along the cable are provided by the Floodline 4 Zone Junction boxes. The zones can be any length but the usual length is between 5 and 15m.
Multi-4 - 4 Zone Detection Cable incorporates a fine multi-filament cellulosic outer covering which acts just like a wick. Water is "sucked" into the inner detection cores allowing the system to react to the smallest drip. A special colour change system is built into the cable giving permanent evidence that the cable has been wet - and where - even after it has dried.
Applications: Attach to the underside of the pipes (inside or outside the lagging) Laid in drip-trays and catchment troughs Fix to soffits and ceilings to detect water ingress
Detection: Activates with any conductive liquid anywhere along the entire length of the detection cable. Once dry can be returned to use in most cases.
Construction: Inner PVC core with cellulosic covered detection cores. Multi-filament cellulosic outer covering.
Dimensions: Oval in shape, 4mm x 6mm
Fixing: For fixing to floor or other surface. Use standard 6mm Tower Clip or self-adhesive clips, or fix to the underside of pipes with tie-wraps or tape inside or outside any lagging.
Click here for all data sheets |
|
|
The Floodline Tundish/Overflow sensor is designed to be attached to the overflow of a toilet cistern or other tank to provide an immediate automatic warning in the event of an overflow.
The sensor can be used singly, or in multiples, connected to any of the Floodline alarm panels. Each sensor can be allocated its own zone, or they can be installed in groups with a number of sensors attached together to form one zone.
The Tundish/Overflow sensor can be easily incorporated into a larger, more complex leak detection installation and it can be used along with any other Floodline detection device.
Tundish/Overflow sensors can be wetted and dried any number of times provided the sensor is not contaminated with a substance that irrevocably changes its electrical characteristics. Any soluble contamination can usually be removed by cleaning the sensor in warm water.
Applications: Toilet cistern and tank overflows
Detection: Activates with any conductive liquid, once dry can be returned to use.
Construction: Tough plastic bowl and connection box with stainless steel sensor probes
Dimensions: Bowl: 65mm diameter x 60mm height Outflow: 20mm length 22mm internal diameter 25.5 external diameter Prefitted leader to connection box: 90mm Connection box: 80mm length 56mm width 24mm height
Fixing: Fix to standard 22mm overflow pipe exiting the cistern/tank
Click here for all data sheets |
|
|
The unique “Multi-Zone” construction of the Multi-8 - 8 Zone water sensitive cable allows up to eight separately reporting detection zones to be provided from one length of cable.
The zone changeover points along the cable are provided by either traditional Floodline 8-zone junction boxes or the Plug And Play system. The zones can be any length but the usual length is between 5 and 15metres.
The sensor can be wetted and dried any number of times provided the cable is not contaminated with a substance that permanently changes its electrical characteristics. If the contamination is soluble then the cable can be removed, washed (clean water only), dried and returned to use subject to the level of contamination.
Applications: Below raised floors Above suspended ceilings Run in drip trays Laid around the base of plant, apparatus or tank Laid in loops or wave pattern for general monitoring of larger areas Attached to pipework within lagging
Detection: Activates with any conductive liquid anywhere along the entire length of the detection cable. Once dry can be returned to use
Construction: A tough, all polymeric, low smoke and fume, zero halogen construction
Dimensions: 5mm Diameter
Fixing: For fixing to floor or other surface, use standard 6mm tower clips, self-adhesive clips or tie-wraps. Detection cable is laid loosely with special Caution Tags attached at regular intervals to identify zone
Click here for all data sheets |
| |
|
|
|